First and second law analyses of wastewater cooled condenser for a refrigeration system

dc.contributor.author Ibrahim Karacayli
dc.contributor.author Lutfiye Altay
dc.contributor.author Arif Hepbasli
dc.contributor.author Karacayli, Ibrahim
dc.contributor.author Hepbasli, Arif
dc.contributor.author Altay, Lutfiye
dc.date.accessioned 2025-10-06T16:22:01Z
dc.date.issued 2019
dc.description.abstract In this study a vapour compression refrigeration (VCR) system with a wastewater (WW) cooled condenser at a temperature range of 27-29 degrees C was designed. The cooling capacity of the system using R134a as the refrigerant was 1.09 kW. The condenser consisted of a coaxial heat exchanger with a capacity of 1 kW. This paper dealt with energy and exergy analyses of the VCR system using WW as a heat sink. Experiments were performed in order to evaluate the energetic and exergetic performances of the wastewater-cooled condenser (WWC) and the overall system. The convective heat transfer coefficient of WW and refrigerant in the condenser overall heat transfer coefficient of the WWC total amount of heat removed by WW amount of cooling effect coefficient of performance (COP) exergy destruction rate and second law efficiencies of the WWC and VCR system were calculated under different WW temperatures and flowrates. Increasing volumetric flowrate of WW from 200 L/h to 400 L/h caused 4.4% improvement in COP 12.0% reduction in exergy destruction and 10.3% increase in exergy efficiency.
dc.identifier.issn 1742-8297
dc.identifier.issn 1742-8300
dc.identifier.uri https://gcris.yasar.edu.tr/handle/123456789/7167
dc.language.iso English
dc.publisher INDERSCIENCE ENTERPRISES LTD
dc.rights info:eu-repo/semantics/closedAccess
dc.source INTERNATIONAL JOURNAL OF EXERGY
dc.subject wastewater, refrigeration, energy, exergy, coefficient of performance, COP, second law efficiency
dc.subject PERFORMANCE
dc.subject Coefficient of Performance
dc.subject Wastewater
dc.subject Refrigeration
dc.subject COP
dc.subject Exergy
dc.subject Second Law Efficiency
dc.subject Energy
dc.title First and second law analyses of wastewater cooled condenser for a refrigeration system
dc.type Article
dspace.entity.type Publication
gdc.author.id Karacayli, Ibrahim/0000-0002-4459-1450
gdc.author.wosid Karacayli, Ibrahim/L-9871-2017
gdc.coar.type text::journal::journal article
gdc.description.department
gdc.description.departmenttemp [Karacayli, Ibrahim] Ege Univ, Ege High Vocat Sch, Air Conditioning & Refrigerat Technol Program, TR-35100 Izmir, Turkey; [Altay, Lutfiye] Ege Univ, Fac Engn, Dept Mech Engn, TR-35100 Izmir, Turkey; [Hepbasli, Arif] Yasar Univ, Fac Engn, Dept Energy Syst Engn, TR-35100 Izmir, Turkey
gdc.description.endpage 171
gdc.description.issue 2-4
gdc.description.publicationcategory Makale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
gdc.description.startpage 155
gdc.description.volume 29
gdc.description.woscitationindex Science Citation Index Expanded
gdc.identifier.wos WOS:000473551500003
gdc.index.type WoS
gdc.wos.citedcount 2
oaire.citation.endPage 171
oaire.citation.startPage 155
publicationissue.issueNumber 2-4
publicationvolume.volumeNumber 29
relation.isOrgUnitOfPublication ac5ddece-c76d-476d-ab30-e4d3029dee37
relation.isOrgUnitOfPublication.latestForDiscovery ac5ddece-c76d-476d-ab30-e4d3029dee37

Files