First and second law analyses of wastewater cooled condenser for a refrigeration system
| dc.contributor.author | Ibrahim Karacayli | |
| dc.contributor.author | Lutfiye Altay | |
| dc.contributor.author | Arif Hepbasli | |
| dc.contributor.author | Karacayli, Ibrahim | |
| dc.contributor.author | Hepbasli, Arif | |
| dc.contributor.author | Altay, Lutfiye | |
| dc.date.accessioned | 2025-10-06T16:22:01Z | |
| dc.date.issued | 2019 | |
| dc.description.abstract | In this study a vapour compression refrigeration (VCR) system with a wastewater (WW) cooled condenser at a temperature range of 27-29 degrees C was designed. The cooling capacity of the system using R134a as the refrigerant was 1.09 kW. The condenser consisted of a coaxial heat exchanger with a capacity of 1 kW. This paper dealt with energy and exergy analyses of the VCR system using WW as a heat sink. Experiments were performed in order to evaluate the energetic and exergetic performances of the wastewater-cooled condenser (WWC) and the overall system. The convective heat transfer coefficient of WW and refrigerant in the condenser overall heat transfer coefficient of the WWC total amount of heat removed by WW amount of cooling effect coefficient of performance (COP) exergy destruction rate and second law efficiencies of the WWC and VCR system were calculated under different WW temperatures and flowrates. Increasing volumetric flowrate of WW from 200 L/h to 400 L/h caused 4.4% improvement in COP 12.0% reduction in exergy destruction and 10.3% increase in exergy efficiency. | |
| dc.identifier.issn | 1742-8297 | |
| dc.identifier.issn | 1742-8300 | |
| dc.identifier.uri | https://gcris.yasar.edu.tr/handle/123456789/7167 | |
| dc.language.iso | English | |
| dc.publisher | INDERSCIENCE ENTERPRISES LTD | |
| dc.rights | info:eu-repo/semantics/closedAccess | |
| dc.source | INTERNATIONAL JOURNAL OF EXERGY | |
| dc.subject | wastewater, refrigeration, energy, exergy, coefficient of performance, COP, second law efficiency | |
| dc.subject | PERFORMANCE | |
| dc.subject | Coefficient of Performance | |
| dc.subject | Wastewater | |
| dc.subject | Refrigeration | |
| dc.subject | COP | |
| dc.subject | Exergy | |
| dc.subject | Second Law Efficiency | |
| dc.subject | Energy | |
| dc.title | First and second law analyses of wastewater cooled condenser for a refrigeration system | |
| dc.type | Article | |
| dspace.entity.type | Publication | |
| gdc.author.id | Karacayli, Ibrahim/0000-0002-4459-1450 | |
| gdc.author.wosid | Karacayli, Ibrahim/L-9871-2017 | |
| gdc.coar.type | text::journal::journal article | |
| gdc.description.department | ||
| gdc.description.departmenttemp | [Karacayli, Ibrahim] Ege Univ, Ege High Vocat Sch, Air Conditioning & Refrigerat Technol Program, TR-35100 Izmir, Turkey; [Altay, Lutfiye] Ege Univ, Fac Engn, Dept Mech Engn, TR-35100 Izmir, Turkey; [Hepbasli, Arif] Yasar Univ, Fac Engn, Dept Energy Syst Engn, TR-35100 Izmir, Turkey | |
| gdc.description.endpage | 171 | |
| gdc.description.issue | 2-4 | |
| gdc.description.publicationcategory | Makale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı | |
| gdc.description.startpage | 155 | |
| gdc.description.volume | 29 | |
| gdc.description.woscitationindex | Science Citation Index Expanded | |
| gdc.identifier.wos | WOS:000473551500003 | |
| gdc.index.type | WoS | |
| gdc.wos.citedcount | 2 | |
| oaire.citation.endPage | 171 | |
| oaire.citation.startPage | 155 | |
| publicationissue.issueNumber | 2-4 | |
| publicationvolume.volumeNumber | 29 | |
| relation.isOrgUnitOfPublication | ac5ddece-c76d-476d-ab30-e4d3029dee37 | |
| relation.isOrgUnitOfPublication.latestForDiscovery | ac5ddece-c76d-476d-ab30-e4d3029dee37 |