First and second law analyses of wastewater cooled condenser for a refrigeration system

Loading...
Publication Logo

Date

2019

Authors

Ibrahim Karacayli
Lutfiye Altay
Arif Hepbasli

Journal Title

Journal ISSN

Volume Title

Publisher

INDERSCIENCE ENTERPRISES LTD

Open Access Color

OpenAIRE Downloads

OpenAIRE Views

Research Projects

Journal Issue

Abstract

In this study a vapour compression refrigeration (VCR) system with a wastewater (WW) cooled condenser at a temperature range of 27-29 degrees C was designed. The cooling capacity of the system using R134a as the refrigerant was 1.09 kW. The condenser consisted of a coaxial heat exchanger with a capacity of 1 kW. This paper dealt with energy and exergy analyses of the VCR system using WW as a heat sink. Experiments were performed in order to evaluate the energetic and exergetic performances of the wastewater-cooled condenser (WWC) and the overall system. The convective heat transfer coefficient of WW and refrigerant in the condenser overall heat transfer coefficient of the WWC total amount of heat removed by WW amount of cooling effect coefficient of performance (COP) exergy destruction rate and second law efficiencies of the WWC and VCR system were calculated under different WW temperatures and flowrates. Increasing volumetric flowrate of WW from 200 L/h to 400 L/h caused 4.4% improvement in COP 12.0% reduction in exergy destruction and 10.3% increase in exergy efficiency.

Description

Keywords

wastewater, refrigeration, energy, exergy, coefficient of performance, COP, second law efficiency, PERFORMANCE, Coefficient of Performance, Wastewater, Refrigeration, COP, Exergy, Second Law Efficiency, Energy

Fields of Science

Citation

WoS Q

Scopus Q

Source

Volume

29

Issue

2-4

Start Page

155

End Page

171
Google Scholar Logo
Google Scholar™

Sustainable Development Goals